- •Instrument transformer burden and accuracy
- •Introduction to protective relaying
- •ANSI/IEEE function number codes
- •Directional overcurrent (67) protection
- •Distance (21) protection
- •Zone overreach and underreach
- •Line impedance characteristics
- •Using impedance diagrams to characterize faults
- •Distance relay characteristics
- •Auxiliary and lockout (86) relays
- •Review of fundamental principles
- •Signal characterization
- •Flow measurement in open channels
- •Material volume measurement
- •Radiative temperature measurement
- •Analytical measurements
- •Review of fundamental principles
- •Control valves
- •Globe valves
- •Gate valves
- •Diaphragm valves
- •Ball valves
- •Disk valves
- •Dampers and louvres
- •Valve packing
- •Valve seat leakage
- •Control valve actuators
- •Pneumatic actuators
- •Hydraulic actuators
- •Electric actuators
- •Hand (manual) actuators
- •Valve failure mode
- •Direct/reverse actions
- •Available failure modes
- •Selecting the proper failure mode
- •Actuator bench-set
- •Pneumatic actuator response
- •Valve positioners
- •Electronic positioners
- •Split-ranging
- •Complementary valve sequencing
- •Exclusive valve sequencing
- •Progressive valve sequencing
- •Valve sequencing implementations
2172 |
CHAPTER 27. CONTROL VALVES |
A photograph showing a pair of progressively sequenced control valves used to control boiler feedwater to the high-pressure (“HP”) drum on a large power boiler is shown here:
One small control valve (horizontal, with a green actuator) is the first to open from 4 to 12 mA. A larger control valve (vertical, with a red actuator) is the next to open from 12 mA to 20 mA. Under normal (full-power) operating conditions, the green valve is wide-open while the larger red valve throttles feedwater to the steam drum. When the boiler is operating in standby (low-power) mode, the red valve is shut while the smaller green valve throttles feedwater to the steam drum. The combination of these two control valves provides better steam drum level control over the boiler’s full range of operation than any single control valve could do alone.
27.11.4Valve sequencing implementations
In all previous control valve sequencing examples shown, both control valves received the same pneumatic signal from a common I/P (current-to-pressure) converter. This means each valve received the exact same pressure signal from the transducer for any given controller output value. Sequencing of the two valves (i.e. making each one respond di erently to the same air pressure signal), therefore, was a matter of setting each valve to a di erent bench-set pressure range.
It should be understood, however, that setting up two control valves with di erent bench-set ranges is not the only way to split-range a pair of valves. Other ways exist as well, each with its own advantages and disadvantages.
27.11. SPLIT-RANGING |
2173 |
The following illustrations depict several alternative methods for control valve sequencing (splitranging):
Common pneumatic signal |
Common electrical signal |
|
PIC |
|
PIC |
101 |
|
101 |
I/P |
I/P |
I/P |
PY |
PY |
PY |
101 |
101a |
101b |
PV-101a |
PV-101b |
PV-101a |
PV-101b |
Dual controller outputs |
Dual controllers |
||
|
PIC |
PIC |
PIC |
|
101 |
101a |
101b |
I/P |
I/P |
I/P |
I/P |
PY |
PY |
PY |
PY |
101a |
101b |
101a |
101b |
PV-101a |
PV-101b |
PV-101a |
PV-101b |