- •Instrument transformer burden and accuracy
- •Introduction to protective relaying
- •ANSI/IEEE function number codes
- •Directional overcurrent (67) protection
- •Distance (21) protection
- •Zone overreach and underreach
- •Line impedance characteristics
- •Using impedance diagrams to characterize faults
- •Distance relay characteristics
- •Auxiliary and lockout (86) relays
- •Review of fundamental principles
- •Signal characterization
- •Flow measurement in open channels
- •Material volume measurement
- •Radiative temperature measurement
- •Analytical measurements
- •Review of fundamental principles
- •Control valves
- •Globe valves
- •Gate valves
- •Diaphragm valves
- •Ball valves
- •Disk valves
- •Dampers and louvres
- •Valve packing
- •Valve seat leakage
- •Control valve actuators
- •Pneumatic actuators
- •Hydraulic actuators
- •Electric actuators
- •Hand (manual) actuators
- •Valve failure mode
- •Direct/reverse actions
- •Available failure modes
- •Selecting the proper failure mode
- •Actuator bench-set
- •Pneumatic actuator response
- •Valve positioners
- •Electronic positioners
- •Split-ranging
- •Complementary valve sequencing
- •Exclusive valve sequencing
- •Progressive valve sequencing
- •Valve sequencing implementations
2142 |
CHAPTER 27. CONTROL VALVES |
These instructions will typically guide you through both the stem connector and the spring adjuster procedures, to ensure both parameters are correctly set.
27.9Pneumatic actuator response
A limitation inherent to pneumatic valve actuators is the amount of air flow required to or from the actuator to cause rapid valve motion. This is an especially acute problem in all-pneumatic control systems, where the distance separating a control valve from the controller may be substantial:
A.S.
Valve position
|
|
|
Time |
|
PV |
|
Pneumatic signal |
SP |
|
from transmitter |
|
|
|
||
|
|
Pneumatic |
Pneumatic actuator |
|
|
controller |
|
|
Out |
|
|
|
|
|
tube |
Controller output signal
Time
The combined e ect of air-flow friction in the tube, flow limitations inherent to the controller mechanism, and volume inside the valve actuator conspire to create a sluggish valve response to sudden changes in controller output signal, not unlike the response of an RC (resistor-capacitor) time-delay circuit where a step-change in voltage input results in an inverse exponential output signal.
27.9. PNEUMATIC ACTUATOR RESPONSE |
2143 |
If the pneumatic valve actuator is driven by an I/P transducer instead of directly by a pneumatic controller, the problem is lessened by the ability to locate the I/P close to the actuator, thus greatly minimizing tube friction and thus minimizing the “time constant” (τ ) of the control valve’s response:
Valve position
|
|
Electronic signal |
Time |
|
|
PV |
|
||
SP |
from transmitter |
Pneumatic actuator |
||
|
||||
|
Electronic |
Air supply |
||
|
|
|||
|
controller |
|
|
|
|
Out |
|
|
|
|
|
wires |
|
|
|
|
I/P |
|
Controller output signal
Time
Still, if the pneumatic actuator is particularly large in volume, an I/P transducer may experience trouble supplying the necessary air flow rate to rapidly actuate the control valve. Certainly the problem of time delay is reduced, but not eliminated, by the close-coupled location of the I/P transducer to the actuator.
One way to improve valve response in either type of system (full-pneumatic or I/P-driven) is to use a device known as a volume booster to source and vent compressed air for the valve actuator. A “volume booster” is a pneumatic device designed to reproduce a pneumatic pressure signal (1:1 ratio), but with far greater output flow capacity. In electrical terms, a volume booster is analogous to a voltage follower : a circuit designed to boost current to a load, without boosting or diminishing voltage. A 3 to 15 PSI pneumatic pressure signal applied to the input of a volume booster will result in an identical output signal (3 to 15 PSI), but with greatly enhanced flow capacity.
2144 |
CHAPTER 27. CONTROL VALVES |
A pneumatic control system equipped with a volume booster would look something like this:
A.S.
Valve position
|
|
Pneumatic signal |
Time |
|
|
PV |
|
||
SP |
from transmitter |
Pneumatic actuator |
||
|
||||
|
Pneumatic |
Air supply |
||
|
|
|||
|
controller |
|
|
|
|
Out |
|
|
tube
Volume
booster
Controller output signal
Time
Of course, enhanced air flow to and from the actuator does not completely eliminate time delays in valve response. So long as the flow rate into or out of an actuator is finite, some time will be required to change pressure inside the actuator and thus change valve position. However, if the actuator volume cannot be reduced for practical reasons of actuating force (larger diaphragm or piston area needed for more force, also resulting in more volume for any given stroke length), then the only variable capable of reducing time lag is increased air flow rate, and a volume booster directly addresses that deficiency.
27.9. PNEUMATIC ACTUATOR RESPONSE |
2145 |
Internally, a volume booster’s construction is not unlike a manually-adjusted pressure regulator14:
Manual-set pressure |
Volume booster |
|
regulator |
||
|
||
setpoint adjust |
Pressure signal |
|
(turn down for more pressure) |
input |
Vent
Regulated air pressure output
screw
spring
diaphragm
spring
Vent
Replicated
air pressure Air supply output
(to actuator)
diaphragm
spring
Air supply
In either mechanism, an internal diaphragm senses output pressure and acts against a restraining force (either a spring preloaded by a hand adjustment screw or an external pressure signal acting on another diaphragm) to position an air flow throttling/venting mechanism. If the output pressure is less than desired, the diaphragm moves down to open the air sourcing plug and supply additional air volume to the output. If the output pressure is greater than desired, the diaphragm moves up to shut o the sourcing plug and open up the venting port to relieve air pressure to atmosphere.
14The volume booster design shown here is loosely based on the Fisher model 2625 volume boosting relay.