7.90. Environmental qualification of safety components that must operate in harsh environments should include type testing.

7.91. When protective barriers are provided to isolate equipment from possible environmental effects, the barriers themselves should be subject to a qualification programme to validate their adequacy.

Internal and external hazards

7.92. I&C systems and components should be protected against the effects of fire and explosion in accordance with the guidance of NS-G-1.7, Ref. [13].

7.93. I&C systems and components should be protected against the effects of other internal hazards in accordance with the guidance of NS-G-1.11 [15].

7.94. I&C systems and components should be designed and qualified to withstand seismic hazards in accordance with the guidance of NS-G-1.6, Ref. [12].

7.95. I&C systems and components should be protected against or designed and qualified to withstand other external hazards in accordance with the guidance of NS-G-1.5, Ref. [11].

Electromagnetic qualification

7.96. The undisturbed operation of electrical and electronic systems and components depends upon their electromagnetic compatibility (EMC) with components located nearby or with which they are connected.

7.97. Electromagnetic compatibility is the ability of a system or component to function satisfactorily in its electromagnetic environment without introducing intolerable electromagnetic disturbances to anything in that environment. An item’s susceptibility to the electromagnetic interference (EMI) and its contribution to the electromagnetic environment (emissions) are both part of EMC. EMI includes Radio Frequency Interference (RFI) and as used in this standard includes electrical surges (for example, voltage spikes resulting from switching transients.

7.98. Significant sources of electromagnetic interference include, for example, fault current clearance by switchgear or circuit breaker or fuse operation, electric fields caused by radio transmitters, natural sources such as lightning strike, and other man-made sources internal or external to the plant.

7.99. Electromagnetic qualification of I&C systems and components depends upon a combination of system and component design to minimize the coupling of electromagnetic noise to electrical components, testing to demonstrate that components can withstand the expected levels, and testing to demonstrate that electromagnetic emissions are within tolerable levels.

7.100. Techniques for minimizing the production and coupling of electromagnetic noise include:

  • Suppression of electromagnetic noise at the source;

  • Separation and isolation of instrument and control signal cables from power cables;

  • Shielding of equipment and cables from external magnetic and electromagnetic sources;

  • Filtering noise before it can couple to sensitive electronic circuits;

  • Neutralization of, or isolation of electronic equipment from ground potential differences; and

  • Proper grounding of electrical and I&C equipment, raceway, cabinets, components, and cables.

7.101. Practices for installation and maintenance must ensure that these provisions are appropriately implemented and maintained.