SET UP MODE

3.1Introduction

To access the Set Up Mode (Levels 2, 3 and 4) the correct password must be entered in the security code frame (the default password code is 0). Refer to the fold-out sheet at the back of this manual for the contents of these levels.

 

LEV2

LEV1

tUnE

Correct Password

OPEr

 

CodE

 

0

 

LEV3

SEtP

Refer to the fold-out sheet for the contents of each level

3.2

Tuning (Level 2)

 

 

 

LEV2

Level 2 – Tuning Level

 

 

tUnE

Note. To select this frame from anywhere in

 

 

 

 

this page, press the

key for a few seconds.

 

 

Cycle Time

 

•1

cYc.1

Heat Time Proportioning Output

 

5.0

[1.0 to 300.0 seconds (<1.0 = 'On/Off' control)]

 

 

 

•2

cYc.2

Cool Time Proportioning Output

 

5.0

[1.0 to 300.0 seconds (<1.0 = 'On/Off control)]

 

 

 

 

HYSt

Continued on next page.

 

 

0.1

 

 

 

 

•1 Only displayed if output 1 is assigned to a relay or logic output. •2 Only displayed if heat/cool hardware configuration is selected.

2-20

…3 SET UP MODE

3.2 Tuning (Level 2) – Fig. 3.2

8

•1 HYSt

0.1

On/Off Hysteresis Value

(used for both heat and cool outputs)

[In engineering units]

PV

Set Point

Hysteresis Value

ON

Reverse Acting

OFF

Control Output

 

Pb-H 100.0

Proportional Band

Enter the proportional band value for the heat and cool outputs.

Heat Output (Output 1)

[0.1% to 999.9%]

•2 Pb-c

100.0

Intr

30

Cool Output (Output 2)

[0.1% to 999.9%]

Continued on next page.

•1 Only displayed if On/Off control is selected for either output. •2 Only displayed if heat/cool hardware configuration is selected.

2-21

8

…3

SET UP MODE

3.2 Tuning (Level 2)

Intr

Integral Action Time

[1 to 7200 seconds or OFF (OFF=0)]

30

 

rSEt

Manual Reset Value

[0% to 100% or –100% to +100% for heat/cool]

50

This value is applied as a bias to the control output.

 

Note. Manual reset is applied with integral

 

action both on and off.

dr1U

Derivative Action Time

[0.1 to 999.9 seconds or OFF (OFF=0)]

1.0

 

•1 0.LAP 0.0

Overlap for Heat/Cool Control

[–20.0% to +20.0%]

This frame defines the portion of the proportional band (Proportional band heat + Proportional band cool) over which both outputs are active – see Fig. 3.1. Neither output is active in the deadband.

A positive value gives an overlap and a negative value a deadband.

•1 Only displayed if a heat/cool hardware configuration is selected.

2-22

3

SET UP MODE…

8

a) Overlap

Pb-h

 

 

 

 

 

 

 

 

Proportional Band (Heat)

 

(%)

Output 1

 

 

Pb-c

 

Power

Proportional Band (Cool)

Output 2 (cool)

(heat)

 

 

 

 

 

 

 

 

Output

Output 2

 

 

 

Output 1 (heat)

(cool)

 

 

 

 

 

 

 

 

 

OLAP

 

Process Variable

 

 

Overlap (positive value)

 

b) Deadband

Pb-h

 

Pb-c

 

(%)

 

 

 

 

Proportional Band Heat

 

Proportional Band Cool

Output Power

Output 1

 

 

 

Output 2

Output 2

 

 

 

Output 1

 

 

 

 

 

 

 

 

 

 

 

 

OLAP

Process Variable

 

 

Deadband (negative value)

 

c) Output 2 on/off control

 

 

 

(%)

 

Pb-h

 

 

 

Output 1

Proportional Band Heat

 

 

Output 2

Output Power

 

 

 

Output 2

O/P2 OFF

O/P2 ON

 

Output 1

 

 

HYSt

 

Process Variable

 

 

ON/OFF' Hysteresis (0% overlap)

 

 

Positive values

 

Negative values

 

 

 

OLAP

 

 

 

 

 

Overlap/Deadband

 

 

Fig. 3.1 Proportional Band & Deadband/Overlap – Heat/Cool Control Only

 

 

 

 

 

2-23